Hawkgas 36 Indoor
Mod Kits
- Corona Rings
Some environments can cause discharge problems on the circuit breaker bushings. To alleviate this problem on pre-1990 units, the corona ring assembly was revised.
- VT Fuses
A new assembly of VT primary fuse mounting was introduced in the year 2000. This is a considerable improvement on earlier assemblies and prevents the possibility of the primary fuses becoming disengaged upon removal of the VT. It is recommended all pre 2000 units have the new assembly fitted.
- Trip Spring
All pre 1996 units should have revised opening spring arrangement, to remove potential for circuit breaker malfunction.